Self-Regulating valve for optimized condensation conditions.
HSX High Pressure Float Valve
HSX high pressure float valves have a shut-off valve welded onto the inlet as well as onto the outlet, as well as a vacuum nozzle and an externally operated transport lock / manual adjustment that can be operated from the outside. In addition, service valves for emptying and discharging non-condensable gases can be installed via two G¼” threaded connections.
Depending on the intended regulation values, the size of the outlet aperture is mechanically opened by means of a float operated valve. The condensed refrigerant is released from the high-pressure side to the low-pressure side and returned to the reservoir.
The transport lock must be “released” before use; this mechanical design operates without electrical power and regular maintenance intervals are not required.
When ordering: – Please specify the intended regulation aperture (-X, -H, -M, -L), the refrigerant type and the application (Qo, to ,tc).
Self-regulating for optimized condensation condition to assist energy-saving operation of refrigeration systems
Technical Specification
Material
steel
Nominal Size
2" - 3"
Nominal Pressure Level
580 psi
Temperature Range for Standard Valves
-76 °F to +167 °F
Connections
butt welding ends as per DIN and ANSI
Additional Information
integrated manual adjustment / transport lock
Video
AWP is competent in the development of individual special solutions for specific requirements. In projects worldwide for numerous industries and international markets, we develop many unique selling points together with the customer.
Our knowledge and experience in the manufacture and development of complex valves and components enable us to provide optimally designed solutions. This innovative support for customers creates potential and synergies from which all parties benefit.